Jyoti Plug-in type
RE-300
& RE-400 Auxiliary Relays are widely used for interlocking
functions in Thermal Power Stations, Petrochemical Complexes and
Cement Plants. They are also used for multiplication of contacts,
voltage selection, anti pumping in circuit breakers and as output
element in PLC Systems. To protect Distribution Network, Electric
Work Motors and Alternators, Jyoti has developed a wide range of Protective and
Auxiliary Relays. These Relays, with solid-state
technology are designed to provide primary protection to rotating
electrical machinery and 11 KV-33 KV distribution feeders. They also
provide back-up protection to HV transmission lines. These relays
are approved by serveral consultants and are used by various
electric utilities.
|
|
Jyoti has developed Microprocessor-based
Temperature
Scanners for monitoring temperature in HT Motors, Alternators, etc.
Modular
Type Scanner 8 channels
Modular Type Scanner 16 channels
- Modular Type
Scanner 8 channels
Function
:
- Monitoring
temperature, pressure, load
Scanner
Type
- 3321
|
|
Voltage
operated Auxiliary relay
Mini Auxiliary Relay
-
Voltage
operated Auxiliary relay
Function
- Voltage operated
Auxiliary operations
Relay Type
- RE-300
Technical
Particulars
:
- With 4 C/O contacts
With plug-in-base suitable for front and rear connection.
With Electromechanical Flag
Coil voltage DC : -
12,24,30,48,50,75,110,127,220,240 & 250 V
Coil burden 4 watts
Pick-up 80%(max)
Coil voltage 24, 30, 36, 110, 115, 127, 150, 220, 230, 240 & 415
VAC, 50Hz.
Coil burden 6 VA (3W)
Pick up 80% (max)
Non-standard voltage coils within the range of 6 V to 250 VDC or upto
415 VAC 50Hz can be supplied against specific requirements.
Applications
:
- Auxillary relay panels
Multiplication of contacts
Voltage selection
Anti-pumping
As an output relay in PLC systems
Fuse failure indication in control circuits
Mini
Auxiliary Relay
Function
- Mini Auxiliary
relay
Relay Type
- RE-400
Technical
Particulars
:
- With 4 C/O contacts
With plug-in-base suitable for front connection
Coil voltage DC : -
12,18,24,30,48,50,75,110,115,220V
Coil burden 2.3 watts *
Pick up 80% (max)
Coil voltage AC, 50 Hz.
- 12,18,24,30,48,50,63.5,110,115,127,
150,220,230,240 V
-
Coil burden 3.5 VA *
Pick up 80% (max)
Applications
:
Auxiliary
relay panels
Multiplication of contacts
Voltage selection
Anti-pumping
As an output relay in PLC systems
Fuse failure indication in control circuits
|
Technical
Particulars
:
- Type of inputs RTD or
T/C or 4-20 mA or 0-5V
Display 7 segment 12.5
mm RED colour LED 3 & 1/2 digit for Temp. & 1 digit for set
point.
Input power
supply110/115220/230/240 VAC (any one) +/- 10%, 50 Hz. +/- 3%, Single
Phase
Accuracy +/- 0.5% of
FSD
No. of relay outputs up to
6 Nos. with 1 NO / 1 NC contact per relay (set points up to 6) or up to
4 Nos. with 1 NO + 1 NC contact (set points up to 4)
Alarm / Trip LED
indication on scanner
All controls and set
points adjustment from Scanner front.
Applications
:
- Used to monitor
temperature, pressure, load, etc. in H.T Motors, Generators,
Alternators, Turbines, Compressors and process control units. These
scanners are suitable for continuous use in industrial environment
- Modular
Type Scanner 16 channels
Function :
- Monitoring
temperature, pressure, load
Scanner
Type
- 3360
Technical
Particulars
:
- No. of inputs RTD or T/C
or 4-20 mA or 0-5 V or combination of two inputs (upto 8 channels each
type)
Display 7 segment 12.5
mm RED colors LED 4,2,1 & 1 digit for Temp. data, channel no., S.P.
No. and limit display respectively & 1 digit for set points.
No. of relay
outputs upto 8 Nos. with 1 NO + 1 NC contact per relay (set points up to
8)
Rest as per model 3321
Applications
:
- Used to monitor
temperature, pressure load, etc. in H.T. Motors, Generators,
Alternators, Turbines, Compressors and process control units. These
scanners are suitable for continuous use in industrial environment.
|