Sr.
No. |
Function |
Relay
Type |
Technical
Particulars |
Applications |
| 1 |
Triple
pole Solid State non-directional IDMTL Over current & Earth
Fault Relay in Draw-out-case
(3 O/C OR 2 O/C + 1 E/F) |
JTRSA |
|
Used
for protection of motors, generators, transformers, distribution
lines and as back-up relay on EHV transmission lines.
|
| 2 |
Single
Pole Solid State non-directional IDMTL in Draw-out case |
JSRSA |
|
- As per
Sr. No. 1 |
| 3 |
Single
Pole Solid State non-directional IDMTL Over current or Earth Fault
Relay in Draw-out-case |
JSRSA |
- With Very Inverse Characteristics
- Rest as per Sr. No. 1
|
- As per
Sr. No. 1 |
| 4 |
Single
Pole Solid State Directional IDMTL Over current or Earth Fault
Relay in Draw-out-case |
JDRSA |
- Max Torque Angle for O/C
- 45 Deg / 30 Deg. Lead
- Max. Torque Angle for E/F
- 45 Deg. Lag
- Rest as per Sr. No. 1
|
- Used
for the ring mains, parallel feeders, parallel transformers, etc. |
- Relays Sr. No. 1 to 4 are also
available without instantaneous unit.
|
| 5 |
Instantaneous
Under / Over voltage relay in Draw-out-case |
PV |
- Voltage Setting Range :
- Under Voltage : 40 to 80% or 30 to 90%
- Over Voltage : 110VAC, 50 Hz
- Nominal Voltage : 110 VAC, 50 Hz
- Aux Supply : 24/30/48/110/220 VDC
- LED Flag Indicators
- Relay with any fix voltage setting also
available
|
- Over
voltage protection of generators, power capacitors, etc.
- Under voltage protection of AC motors.
- Automatic voltage change over schemes.
|
| 6 |
Definite
Time Lag Under / Over Voltage relay in Draw-out-case |
SPVK |
- Time range : 0.05 Sec to 120
Secs.
- Rest as per Sr. No. 5
|
- As
above |
| 7 |
Instantaneous
electro-mechanical 3 -pole current operated relay |
PA |
- With three current measuring elements RMA
- Current Ranges
0.006 to 0.024 - 1.5 to 6.0
0.024 to 0.096 - 2.4 to 9.6
0.06 to 0.24 - 3.0 to 12.0
0.075 to 0.30 - 4.5 to 18.0
0.2 to 0.8 -
6.0 to 24.0
0.3 to 1.2 -
12.0 to 48.0
0.6 to 2.4 -
18.0 to 72.0
1.2 to 4.8 -
24.0 to 96
- With LED indicators
- With one output
relay RE - 300 (AC/DC)
- Aux Voltage : 24/30/50/110/127/220 VDC
: 110/240 VAC, 50 Hz.
- With plug-in base (Case ref. EGE-301)
- Two Pole & Single Pole relays are
also available
|
- Over
current & Earth fault protection of feeders, transformers,
motors, alternators, etc.
- Sensitive earth fault protection in isolated /ineffectively
earthed system
- Restricted earth fault protection of transformers / generators
- Differential protection of generators / motors
|
| 8 |
Definite
Time Lag Current Operated Relay |
SPAK
|
- With three current measuring elements RMA
- Current Ranges as per Sr. No. 5 but
highest 6 to 24 Amps.
- With one unit of time delay relay type
SRT-11C
(Aux. Supply : 24/30/48/110/127/220 VDC)
- Time Ranges :
0.1 to 2.0 secs
0.3 to 6.0 secs
0.5 to 10.0 secs
1.0 to 20.0 secs
1.25 to 25.0 secs
- With LED indicators
- With plug-in base (case ref. EGE-301)
- Two Pole & Single Pole relays are
also available.
|
- Time
graded over current & earth fault protection of motors, alternators, transformers, etc.
- Definite time over current protection against phase & earth
fault on medium & low voltage distribution systems.
- Sensitive earth fault protection.
- Stalling protection of motors.
- Overload protection for motor feeders. |
| 9 |
Solid
state trip circuit supervision relay |
JTS-11
JTS-10 |
- With supervision under breaker 'ON' and
breaker 'OFF' condition
- With LED Indicator (H/R)
- Aux. Supply 24/30/50/110/127/220 VDC
- Case ref. EGE-201
- With supervision only under breaker 'ON'
condition
- Rest as per Sr. No. 9
|
- Used
for supervision of a circuit breaker, for initiation of alarm and
visual indication if the trip circuit fails or the circuit breaker
mechanism does not operate. |
| 10 |
Solid
state time delay relay with delay on pickup or drop-off |
SRT-11C
SRT-22 |
- Aux. supply 24/30/50/110/127/220 VDC
- With LED indicator (H/R)
- Times ranges :
0.05 to 1.0 - 1 to 20
0.1 to 6.0 - 3 to 30
0.3 tp 6.0 - 6 to 120
0.5 to 10.0 - 15 to 300
- Case ref. EGE-201
|
Used
for time graded selective protection and industrial processes
where a large number of operations are required with high
reliability and consistent accuracy. |
| 11 |
Power
Unit |
JDL-110 |
- With trip circuit healthy and DC healthy
indicators (For captive tripping of circuit breakers)
- With 20 watt-sec output energy
- Input Voltage 110/240 VAC, 50 Hz.
- Output Voltage 110 VDC
- Without plug-in-base (Case ref. EGE-301)
|
- Where
provision of station batteries is not economical, power unit is
used for energizing trip coil of the circuit breaker. |
|
|
JDK-110 |
- With 20 watt-sec output energy and built
in RE-300 relay
|
|
| 12 |
Voltage
operated Auxiliary Relay |
RE-300 |
- With 4 C/O contacts
- With plug-in-base suitable for front and
rear connections
- With Electromechanical Flag
- Coil voltage DC : -
12,24,30,48,50,75,110,127,220,240 & 250 V
- Coil burden 4 watts
- Pick-up 80%(max)
- Coil voltage AC, 50 Hz.
24, 30, 36, 110,115,127,150,220,230,240 415 V
- Coil burden 6 VA (3W)
- Pick up 80% (max)
- Non-standard voltage coils within the
range of 6V to 250V or up to 415 VAC, 50 Hz. can be supplied
against specific requirements (anyone)+/- 10%, 50Hz +/- 3%,
Single Phase.
|
-
Auxiliary relay panels
- Multiplication of contacts
- Voltage selection
- Anti-pumping
- As an output relay in PLC systems
- Fuse failure indication in control circuits
|
| 13 |
Mini
Auxiliary relay |
RE-400 |
- With 4 C/O contacts
- With plug-in base suitable for front
connection
- Coil voltage DC:
12,18,24,30,48,50,75,110,115,220 V
- Coil burden 2.3 watts
* Pick up 80%
(max)
- Coil voltage AC, 50 Hz.
- 12, 18, 24, 30, 48, 50, 63 5, 110, 15, 127, 220, 230, 240 V
- Coil burden 3.5 VA * Pick-up 80% (max)
- Non-standard voltage coils within the
range of 6V to 250V or up to 415 VAC, 50 Hz. can be supplied
against specific requirements anyone)+/- 10%, 50Hz +/- 3%,
Single Phase.
|
-
Auxiliary relay panels
- Multiplication of contacts
- Voltage selection
- Anti-pumping
- As an output relay in PLC systems
- Fuse failure indication in control circuits
|
| 14 |
Modular
type scanner up to channels |
3321 |
- Type of inputs RTD or T/C or 4-20 MA or
0-5V
- Display 7 segment 12.5 mm RED
color LED
3 1/2 digit for Temp. & 1 digit for set point.
- Input power supply110/115220/230/240 VAC
- No. of relay outputs
up to 6 Nos. with 1
NO / 1 NC contact per relay (set points up to 6) or up to 4 Nos.
with 1 NO + 1 NC contact (set points up to 4)
- Alarm / Trip LED indication on scanner
- All controls and set points adjustment
from Scanner front.
|
- Used
to monitor temperature, pressure, load, etc. in H.T Motors,
Generators, Alternators, Turbines, Compressors and process control
units. These scanners are suitable for continuous use in
industrial environment |
| 15 |
Modular
type scanner up to 16 channels |
3360 |
- No. of inputs RTD or T/C or 4-20 MA or
0-5 V or combination of two inputs (up to 8 channels each type)
- Display 7 segment 12.5 mm RED
color LED
4,2,1 & 1 digit for Temp. data, channel no., S.P. No. and
limit display respectively & 1 digit for set points.
- No. of relay outputs
up to 8 Nos. with 1
NO + 1 NC contact per relay (set points up to 8)
- Rest as per model 3321
|
- Used
to monitor temperature, pressure load, etc. in H.T. Motors,
Generators, Alternators, Turbines, Compressors and process control
units. These scanners are suitable for continuous use in
industrial environment. |
|