| Switch Gears - Features |
| |
| Vacuum Circuit Breaker |
| |
 |
A compact, light weight construction, optimized to give minimum weight to KA ratio.
|
A unique 'U' shaped insulation barrier housing the Vacuum interrupters, (except for VK 10 Q 40) imparting maximum mechanical strength against electrodynamic forces and provides most effective phase to phase and phase to earth segregation.
|
A simple motor charged spring operating mechanism noted for its high performance reliability. |
A versatile mechanism capable of operating Vacuum Interrupters of any type. Hence, dependence on single source of Vacuum Interrupters eliminated. |
 |
Trip free mechanism suitable for repeated auto re closing duty
. |
Spring charging time of less than 10 seconds. Totally enclosed construction for spring charging motor.
|
Built-in manual charging handle with every circuit breaker for effortless manual spring charging. |
 |
Easy visual check of contact erosion
|
Superior mechanical endurance limit. Maintenance required only after 10,000 operations. |
|
| |
| Inside the Cubicle |
|
 |

|
Fully segregated circuit breaker compartment ensures that no arc product or foreign body can travel from or to cable and bus bar compartment. |

|
A screw type racking arrangement for easy insertion and withdrawal of the Circuit Breaker renders perfect contact pressure, independent of operator's force. |

|
A positive interlock to ensure the circuit breaker insertion to or withdrawal from SERVICE position only when it is OPEN. |
|
| |
|
|
| Retrofit (Indoor MOCB Panel) |
 |
| |
|
| |
 |
| Rear & front view of One-to-One VCB |
|
| |
RETROFIT SOLUTIONS FROM JYOTI |
| |
In the 1950s to 1990 MOCBs were the mainstay of switching devices for medium power generation and distribution networks. Jyoti was first to introduce the concept of replacing old MOCBs with latest VCB technology thereby increasing the service life of the existing switchgear panels. Retrofit solutions for their MOCBs as well for other make MOCBs.
This year Jyoti has successfully designed, developed and commissioned retrofit solution for NGEF 12kV, 1250 Amp 25kA MOCB type EKU 5012 at a public sector refinery in western India. The retrofit solution has been completed one month ahead of schedule with successful commission and taking on load of 19 numbers vacuum breakers on 17th May 2010.
As of now Jyoti has more than 2000 retrofit breaker in service. |
| |
 |
 |
 |
| EKU 5012 RETROFIT |
EXACT MATCH |
VCB INSIDE PANEL |
|
| |
 |
 |
| OUR TEAM |
RETOFIT VCBs READY FOR INSERTION INPANELS |
|
| |
| |
| Busbars |
|
 |
between phases or phase to earth, even if bridged by vermin or any other conducting body.
|
 |
Flexible insulating shrouds cover the bus bar to jumper joints and jumper to stationery contact joints
|
 |
Eproxy molded stationary disconnect contacts prvide effective segregation between phases and phase to earth.
|
 |
Bus bars and jumpers are covered with special heat shrink sleeves which provide effective insulation
|
 |
A separate segregated compartment for voltage transformers. Voltage transformer connections through epoxy molded contacts.
|
 |
Withdraw able voltage transformer truck arrangement. |
 |
Automatic safety shutters cover the live parts when voltage transformer is withdrawn outside the crucible.
|
 |
Adequate space for entry and termination of two sets of 3-core or 6 nos. (2 per phase of single core) cable connections.
|
 |
Additional sets of cables or current transformers can be housed within modular rear extension.
|
|
|
| |
| Vacuum Contactor - (Indoor |
 |
A compact , light weight construction, optimized to give minimum weight.
|
 |
Excellent Choice for switching motors transformers and Capacitors.
|
 |
Available In two versions Electrical and Mechanicals. |
 |
Exceptionally High mechanical and electrical life( In million operations) |
 |
Low Chopping Current ( maximum 1.5 Amp and Avg 0.9 Amp) |
 |
Suitable for High Switching frequency ( around 300 operations per hour)
|
 |
Cheaper / cost saving device for motor , transformer and capacitor switching.
|
 |
Suitable for 3.3kv / 6.6kV 400 Amp. |
|
 |
|
| |
| |